화학공학소재연구정보센터
Journal of Loss Prevention in The Process Industries, Vol.14, No.6, 567-574, 2001
Unified correlations for vent sizing of enclosures at atmospheric and elevated pressures
Innovative vent sizing technology is presented for explosion safety design of equipment at atmospheric and elevated initial pressures. Unified correlations for vent sizing are suggested. They are modifications of previously reported correlations verified thoroughly for experimental data on vented gaseous deflagrations under different conditions but only at initial atmospheric pressure. Suggested correlations are based on experimental data on vented deflagrations of quiescent and turbulent propane-air mixtures at initial pressures up to 0.7 MPa. Typical values of turbulence factor and deflagration-outflow interaction number are obtained for experimental vented deflagrations at initial pressures higher than atmospheric. "Blind" examination of new vent sizing technology on another set of experiments with methane-air and propane-air mixtures has shown that predictions by suggested vent sizing technology are better than by the NFPA 68 guide for "Venting of Deflagrations". In the development of recently reported results for initial atmospheric pressure it has been concluded that the innovative vent sizing technology is more reliable compared to the NFPA 68 guide at elevated initial pressures as well. Moreover it is crucial that the calculation procedure remains the same for arbitrary deflagration conditions.